SafEye Duct

SafEye-DustThe Duct SafEye Open Path was specially designed and is widely used to monitor and alarm against ingress of hazardous gas concentrations into air intakes of turbine engines and HVAC air ducts. Formation and migration of gas clouds and their possible penetration into safe places, control rooms, turbine engines, etc. is a substantial risk that needs to be addressed.

Users, designers, safety and operational engineers are increasingly required to provide for adequate and fast detection and alarm to protect these hazards.

The specific system’s design for duct applications requires that the small path across an air inlet responds with a very high sensitivity, full scale of 1 LEL.m for 2-6.6 ft. (0.6-2 m) wide inlet and full scale of 2.5 LEL.m for 6.6-23 ft. (2-7 m) wide inlet.

The Duct SafEye, due to its special optics design, provides for a misalignment tolerance of ±2° in all directions and is protected against false gas reading and alarms which are caused by partial obscuration and blocking, misalignment, vibration, flexing or tilts.

Each SafEye unit is factory calibrated in a temperature cycle run at the entire operating temperature range. The temperature compensating mechanism allows correct operation in changing and extreme temperatures while maintaining the system’s accuracy. Its internal microprocessor will automatically compensate for low signals with its internal Automatic Gain Control (AGC).

 

KEY FEATURES

  • Proven Technology
    • Used in air ducts on FPSO’s and offshore rigs for British Petroleum (BP), Shell and ABB Lummus for turbines air intakes etc.
  • High Sensitivity
    • Alarm up to 0.5 LEL.m
    • 5 Times more sensitive than the normal Open Path equipment
  • Fast Response
    • Fast response time of 2 seconds (300 series) and ultra fast response of 1 second (200 series).
    • 5 to 10 times faster than commonly used Open Path, 20-50 times faster than Point Detector.
  • Harsh Environment

Specially designed to perform under extreme conditions such as high-speed airflows, high temperatures (up to 158˚F (70˚C)), humidity and corrosive gases, where point detectors may not be effective.

  • Low Maintenance

High reliability, simple installation, alignment and maintenance, equipment not subject to poisoning.

  • Standard Interface Options

Standard 4-20 mA outputs or RS-485 output to allow networking (up to 64 detectors) to a central monitoring/PC system. This feature also enables easy maintenance, local and remote diagnostic tools.

 

APPLICATIONS

  • Offshore Oil & Gas Exploration Oilrigs and FPSOs
  • Onshore Oil & Gas Terminals
  • Storage Farms and Filling Stations
  • Petrochemical and Chemical Industries
  • Power Utilities and Turbines areas

 

SPECIFICATIONS

Detection Range and Response Time
Model
202FD 301FD 302FD
Distance (m) 2-7 0.6-3.5 3-15
Response Time 1 sec. 2 sec. 2 sec.
Detected Gases Simultaneous detection of C1 -C8  flammable gases.
Immunity to False Alarm Is not influenced by solar radiation, hydrocarbon flames and other external IR radiation sources, high airflows and high loaded streams.
Spectral Response 3.0-4.0 µm
Sensitivity Range 0-2.5 LEL.m Standard
0-1 LEL.m by dip-switch setting
Displacement/Misalignment Tolerance ±2˚
Drift Long-term ±5% of full scale
Temperature Range -40˚F (-40˚C) to 131˚F (55˚C) for Series 200
-40˚F (-40˚C) to 158˚F (70˚C) for Series 300
Power Supply Standard - 24 VDC (18-32 VDC)
Power Consumption Detector: 150mA @ 24 VDC (200 mA Peak)
Source:   100mA @ 24 VDC (220 mA Peak)
Electrical Connection 2 x 3/4˝ - 14NPT conduits or 2 x M25 x 1.5 mm ISO
Electrical Input Protection Complete electrical interface protection against reversed polarity voltage, surges and spikes according to MIL-STD-1275A
Electromagnetic Compatibility EMI/RFI protected CE Marked
Outputs - 4-20mA The 4-20mA current output is source configuration
Resistance Loop 100-600 Ω
Outputs - RS-485 Serial communication for full control with maintenance and trouble shooting facility can be integrated for a network of max 64 detectors
Outputs - Relays
  Type Normal Position Maximum Ratings
Alarm SPDT NO, NC 2A at 30VDC or 0.5 at 250 VAC
Accessory SPST Open 5A at 30VDC or 250VAC
Fault SPST Closed 5A at 30VDC or 250 VAC
Approvals
ATEX / Cenelec: EX II 2G EExd IIB + H2 T5 (70˚C), T6 (55˚C). EX II 2G EExde IIB + H2 T5 (70˚C), T6 (55˚C).
UL: UL No. - E209870, Class I Groups C and D Hazardous Location
Water and Dust Tight IP66 and 67
NEMA 250 6P
Mechanical Design The standard detector housing is heavy-duty, copper-free (less than 1%) aluminum. The housing is finished in white epoxy enamel and is also available in 316L Stainless Steel upon request.
Environmental Standards Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical shock, High Temp, Low Temp
Dimensions 5.2" (132mm) x 5.2" (132mm) x max. 4.7" (120mm)
Weight Al. Encl. Detector: max 8.1 lb (3.7 kg) Source: max 8.58 lb (3.9 kg)
St. Encl. Detector: max 13.4 lb (6.1 kg) Source: max 13.84 lb (6.3 kg)

 